EAc7 Enhanced Refrigerant Management
Reduce refrigerant climate impact through no/low-GWP equipment, leakage controls, and/or qualifying food-retail certification.1
Reviewed · Spot an error? Report it
Points
NC and Core and Shell: maximum 2 points. No-refrigerant path 1; low-GWP path 1 at no more than 80% of benchmark or 2 at no more than 50%; leakage option 1. GreenChill Silver 1, Gold/Platinum 2, within the cap.1
Exemplary performance: A total weighted average refrigerant GWP of 25 or less across all new refrigerant-containing equipment under Option 1 earns 1 exemplary performance point; Core and Shell projects qualify only when included equipment totals at least 2.5 Btu/h per ft² (8 W/m²) of conditioned floor area or at least 50% of the combined refrigerant equipment capacity serving the project, claimed under Project Priorities (EP8).2
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- New-equipment refrigerant inventory with charge, equipment class, GWP, and weighting
- Benchmark/adjusted-benchmark comparison workbook
- Leak-detection design and refrigerant piping specifications
- Refrigerant maintenance, oversight, inspection, and repair plan
- GreenChill certification and food-retail area calculation, if used
Worked example
Assume only HVAC equipment, so the applicable benchmark is 700, and a correctly weighted proposed GWP of 350. Relative GWP = 350/700 × 100 = 50%, reaching the 2-point low-GWP band, provided the inventory, weighting, and eligibility are valid.1
Requirements
The low-GWP path compares the total weighted-average refrigerant GWP in new equipment with weighted benchmarks for the applicable equipment classes; adjusted benchmarks can reflect reduced charge per capacity. Leakage achievement requires the specified design, piping/fitting, detection, maintenance, oversight, and inspection provisions. Core and Shell has scope-eligibility conditions. GreenChill applies where food retail is more than 20% of gross area; international projects follow the relevant program requirements. District-energy provisions also apply.1
FAQ
Does an unbuilt tenant HVAC system make a Core and Shell project refrigerant-free?
The no-refrigerant option excludes Core and Shell projects lacking future equipment needed to meet the project's heating or cooling load.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 BD+C Rating SystemJuly 2026 · EAc7, printed pp. 123-125
- USGBC LEED credit library: Enhanced Refrigerant Management: Exemplary Performance (EP8)Published Apr 21, 2025; retrieved November 8, 2026 · EP8 requirements
Maintained by VERTIQ, LEED software for consultants.