Credit Enhanced Refrigerant Management

Use no/low-impact refrigerants or document the equipment-weighted lifecycle refrigerant impact.1

Points
1 point
Applies to
BD+CID+C
Other versions
v4v5
VERTIQ reference ID
EAc6

Reviewed · Spot an error? Report it

Points

1 point.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Complete refrigerant/equipment schedule
  • Refrigerant ODP/GWP declarations
  • Lifecycle impact worksheet and management plan where selected
  • Retail GreenChill or leakage/charge records where applicable
  • Confirmation that project HVAC&R systems comply with ASHRAE Standard 15 where Option 2 is used

Worked example

Assume every applicable system uses a refrigerant with ODP = 0 and GWP = 40. Since 40 < 50, the refrigerant values meet Option 1. One additional system using GWP 500 would prevent that all-system route, even if the building average were below 50.1

Requirements

The low-impact route requires ODP of zero and GWP below 50 for all applicable refrigerants. The calculation route applies ASHRAE 15-2019 or approved equivalent, a refrigerant management plan for systems above 0.5 lb/225 g, and the capacity-weighted lifecycle ozone/GWP calculation using the stated defaults and units. Retail commercial refrigeration has additional charge, leak-testing and emissions requirements or the permitted GreenChill certification route.1

FAQ

Is the low-GWP route assessed as a building average?

It calls for no refrigerants or only refrigerants meeting the ODP/GWP criteria. The weighted lifecycle calculation is a separate option.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 87-89