Credit Enhanced Refrigerant Management
Use no/low-impact refrigerants or document the equipment-weighted lifecycle refrigerant impact.1
- Points
- 1 point
- Applies to
- BD+CID+C
- VERTIQ reference ID
- EAc6
Reviewed · Spot an error? Report it
Points
1 point.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Complete refrigerant/equipment schedule
- Refrigerant ODP/GWP declarations
- Lifecycle impact worksheet and management plan where selected
- Retail GreenChill or leakage/charge records where applicable
- Confirmation that project HVAC&R systems comply with ASHRAE Standard 15 where Option 2 is used
Worked example
Assume every applicable system uses a refrigerant with ODP = 0 and GWP = 40. Since 40 < 50, the refrigerant values meet Option 1. One additional system using GWP 500 would prevent that all-system route, even if the building average were below 50.1
Requirements
The low-impact route requires ODP of zero and GWP below 50 for all applicable refrigerants. The calculation route applies ASHRAE 15-2019 or approved equivalent, a refrigerant management plan for systems above 0.5 lb/225 g, and the capacity-weighted lifecycle ozone/GWP calculation using the stated defaults and units. Retail commercial refrigeration has additional charge, leak-testing and emissions requirements or the permitted GreenChill certification route.1
FAQ
Is the low-GWP route assessed as a building average?
It calls for no refrigerants or only refrigerants meeting the ODP/GWP criteria. The weighted lifecycle calculation is a separate option.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 87-89