Credit Enhanced Refrigerant Management
Minimize refrigerant ozone-depletion and climate impacts beyond the CFC prerequisite.1
- Points
- 1 point
- Applies to
- BD+CID+C
- VERTIQ reference ID
- EAc6
Reviewed · Spot an error? Report it
Points
1 point.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Refrigerant equipment schedule with equipment tag per drawings, equipment type and quantity, refrigerant type, charge, cooling capacity and equipment life
- Manufacturer ODP/GWP documentation
- Life-cycle refrigerant calculation if using Option 2
- Retail commercial refrigeration specifications with leak test results or GreenChill certification, if applicable
Worked example
Assume every nonexempt system uses a verified refrigerant with ODP = 0 and GWP = 3. Since 3 < 50, it meets the refrigerant-property screen for Option 1; equipment coverage and the remaining conditions must still be checked.1
Requirements
Choose no refrigerants/only refrigerants with zero ODP and GWP below 50, or complete the specified life-cycle refrigerant impact calculation across the relevant new/existing base-building and tenant systems. Apply capacity weighting across multiple equipment types. Retail commercial refrigeration has a separate compliance path.1
FAQ
Is passing the CFC prerequisite enough?
No. This credit adds its own low-impact or calculated-impact requirements.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.