Prerequisite Fundamental Refrigerant Management

Avoid CFC refrigerants in new HVAC&R equipment and address CFCs when reusing existing systems.1

Points
Required
Applies to
ID+CBD+C
Other versions
v4.1v5
VERTIQ reference ID
EAp3

Reviewed · Spot an error? Report it

Points

Required prerequisite, with no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Refrigerant/equipment schedule identifying new, reused and exempt units.
  • Preparation checklist: CFC conversion records or a justified extended phase-out proposal where needed.

Worked example

Assume an existing unit contains 0.4 pound of refrigerant. It is below the 0.5-pound small-unit boundary. That exemption does not excuse a separate large reused CFC chiller serving the tenant.1

Requirements

No CFC-based refrigerants may be used in new HVAC&R systems. For reused existing equipment, complete comprehensive CFC conversion before project completion; later phase-out plans are considered on their merits. Existing small units and other equipment containing less than 0.5 pound (225 grams) of refrigerant are exempt.1

FAQ

Does the exemption cover a unit containing exactly 0.5 pound?

The text says less than 0.5 pound; equality is outside that exception.1