Credit Enhanced Refrigerant Management

Choose low-impact refrigerants or calculate the combined refrigerant impact of equipment serving the tenant.1

Points
1 point
Applies to
ID+CBD+C
Other versions
v4.1v5
VERTIQ reference ID
EAc5

Reviewed · Spot an error? Report it

Points

1 point for one complete applicable route.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Equipment/refrigerant schedule, tags, charge, capacity, ODP/GWP and life assumptions.
  • Preparation checklist: Lifecycle-impact calculation and Retail leak testing or GreenChill certification if applicable.

Worked example

Assume a CI Option 2 system has ODP=0, GWP=1,000, annual leakage 0.02, end-of-life loss 0.10, life 10 years and charge 2 lb/ton. LCGWP = 1,000 x (0.02 x 10 + 0.10) x 2 / 10 = 60 lb CO2/ton-year; LCODP=0. The IP result 60 is below 100. Include every applicable system before concluding compliance.1

Requirements

For CI/Hospitality, Option 1 uses no refrigerants or only refrigerants with zero ODP and GWP below 50. Option 2 limits capacity-weighted lifecycle climate plus ozone impact to 100 in IP units or 13 in SI units, including new/existing base-building and tenant HVAC&R serving the project.1

Retail meets Option 1 or 2 for HVAC. Commercial refrigeration also requires non-ozone-depleting refrigerants, limited HFC charge, annual emissions no more than 15%, and installation leak testing; qualifying EPA GreenChill Silver certification for newly constructed stores is an alternative for those systems.1

FAQ

Can the base-building systems serving the tenant be omitted?

Option 2 includes both base-building and tenant HVAC&R that serves the project.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4 for Interior Design and ConstructionUpdated July 25, 2019 · Enhanced Refrigerant Management; printed and PDF pp. 35-37