Credit Enhanced Commissioning
ID+C enhanced commissioning earns 4 points, or 5 with monitoring-based commissioning.1
Reviewed · Spot an error? Report it
Points
Option 1: 4 points. Option 2: 5 total, not 4 plus 5.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: CxA independence and experience evidence; enhanced commissioning plan and submittal reviews.
- Preparation checklist: Training/manual delivery, seasonal tests, ten-month review, ongoing plan and monitoring records if used.
Worked example
Assume Option 1 is complete and the monitoring procedures, points and quarterly analyses are also complete. The monitoring option is 5 points total. Four quarterly analyses over one year illustrate the minimum analysis frequency, but do not establish the remaining tasks.1
Requirements
Use the enhanced CxA independence criteria stated with Fundamental Commissioning and Verification. Option 1 adds contractor-submittal review, systems-manual and training requirements and verification, seasonal testing, a ten-month operations review and an ongoing commissioning plan.1
Option 2 includes Option 1 and monitoring-based procedures for energy/water systems, measurement points, responsibilities, trends, acceptable values, fault correction and training. Analyze at least quarterly during the first occupancy year and update the systems manual for changes.1
FAQ
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 for Interior Design and ConstructionUpdated July 25, 2019 · Enhanced Commissioning; printed and PDF pp. 27-28
- LEED v4 Reference Guide for Interior Design and Construction AddendaCumulative through February 20, 2026 · PDF pp.12-13, Reference Guide p.115 CxA oversight and July 2, 2018 removal of BD+C envelope exception