Credit Optimize Energy Performance
Improve modeled building energy performance using the criteria applicable to the project's registration date.1
Reviewed · Spot an error? Report it
Points
Option 1: up to 18 points generally, 16 for Schools, 20 for Healthcare. Use the appropriate adaptation column; the published update tables do not have a separate Retail column.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Baseline and proposed Appendix G model reports
- Energy cost/source-energy and GHG calculation outputs
- Design-phase energy target and efficiency-option analysis
- Renewable generation and allocation documentation where claimed
Worked example
Assume a New Construction project registered after March 1, 2024 with a 30% cost improvement and 35% GHG improvement, after applying the permitted modeling rules. Table 1 gives 3 points and Table 2 gives 4, for 7 points. This is not the original pre-update single-metric table.1
Requirements
For projects registered from March 1, 2024, Option 1 compares the proposed design with ASHRAE 90.1-2010 Appendix G. Add the points from Table 1, using cost or source energy, to Table 2, using greenhouse gas emissions. Set the source-energy performance target by schematic design and analyze efficiency opportunities during design.1
On-site renewable energy can affect both tables under G2.4. Qualifying new off-site/community renewable energy can affect the GHG credit calculation, but cannot satisfy the prerequisite. Earlier registrations use the original v4 criteria, not these updated tables.1
Original criteria for registrations before March 1, 2024: Option 1 uses one percentage improvement against ASHRAE 90.1-2010 Appendix G. New Construction thresholds for 1 to 18 points are 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 29, 32, 35, 38, 42, 46 and 50%. Major Renovation runs from 4% to 48% and Core and Shell from 3% to 47%. At each threshold Healthcare earns 2 more points, up to 20, and Schools stop at 16. Option 2, available to projects using Option 2 of the Minimum Energy Performance prerequisite, follows the ASHRAE 50% Advanced Energy Design Guide for 1-6 points. Data Centers follow their own simulation criteria.2
FAQ
Did the 2024 update change the reference standard to 90.1-2016?
No. The v4 update keeps 90.1-2010 Appendix G; v4.1 is a different rating-system path.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- USGBC Optimize Energy Performance (2024 Update), BD+C v42024 Energy Update; official language captured October 23, 2026 · Option 1, Tables 1-2, registration-date and renewable-energy notes
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Optimize Energy Performance, printed/PDF pp. 73-75
Maintained by VERTIQ, LEED software for consultants.