EQc4 Resilient Spaces

Design operational modes and passive or operable-space strategies that protect occupants during disruptive events.1

Points
See below
Applies to
ID+CBD+CO+M

Reviewed · Spot an error? Report it

Points

Maximum 3 points. Each event-management mode earns 1; heat and cold safety paths earn 1 each; operable windows earn 1 at 50% coverage or 2 at 75%. Do not add above the overall cap.1

Exemplary performance: achieving any additional option earns 1 exemplary performance point, claimed under Project Priorities (EP20).3

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation: Operating-mode sequences and commissioning verification
  • Preparation: Thermal-outage model and designated safety zones if selected
  • Preparation: Operable-window schedule and space-coverage calculation

Worked example

Assume 16 of 20 regularly occupied spaces have operable windows meeting ASHRAE 62.1-2022 size and location requirements. Coverage = 16 / 20 x 100 = 80%, above 75%, for 2 points. A separate compliant respiratory-disease mode adds 1 point, giving the 3-point maximum.1

Requirements

Options 1 and 2 provide commissioned management modes for episodic outdoor events under ASHRAE Guideline 44 and respiratory diseases under ASHRAE 241-2023, respectively. Document and verify the modes in design and commissioning.1

Option 3 uses thermal modeling to show designated safety zones remain passively habitable during a two-day outage at peak summer and/or winter conditions. Passive House certification is also listed for the cold path. Option 4 provides compliant operable windows to 50% or 75% of regularly occupied spaces for 1 or 2 points.1

FAQ

Is the total cap 2 points?

No. The July 2026 Rating System and July 31 correction identify a 3-point cap.12

Is the outage analysis for a full year?

The thermal-safety paths specify a two-day outage during peak seasonal conditions in a typical meteorological year.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 ID+C Rating SystemJuly 2026 · EQc4; printed pp. 101-102, PDF pp. 106-107; scorecard printed pp. 1-2, PDF pp. 6-7
  2. LEED v5 ID+C Addenda Table, cumulativeJuly 31, 2026; individual post dates identified in locator · PDF p. 9, EQc4 Requirements first sentence, July 31, 2026: 2-point wording changed to 3 points
  3. USGBC LEED credit library: Resilient Spaces: Exemplary Performance (EP20)Published Apr 22, 2025; retrieved November 8, 2026 · EP20 requirements

Maintained by VERTIQ, LEED software for consultants.