EQc4 Resilient Spaces

Protect occupants during adverse outdoor air, respiratory-disease events, extreme weather outages, or loss of mechanical ventilation through the eligible resilience paths.1

Points
See below
Applies to
BD+CID+CO+M

Reviewed · Spot an error? Report it

Points

NC and Core and Shell maximum 2 points. Each NC management-mode option earns 1. Summer and winter thermal-safety paths each earn 1. Operable windows earn 1 at 50% or 2 at 75% of regularly occupied spaces.1

Exemplary performance: achieving any additional option earns 1 exemplary performance point, claimed under Project Priorities (EP20).2

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Resilience management-mode sequences and commissioning verification
  • Two-day thermal-outage model (or Passive House certification for the cold path) and thermal-safety-zone plans for selected heat/cold paths
  • Regularly occupied space register, operable-window schedule and coverage calculation, and ASHRAE 62.1 opening-area and distance calculations

Worked example

Assume 20 equal-size regularly occupied spaces, and 15 have qualifying operable windows. Coverage is 15/20 × 100 = 75% both by space count and by area under this example assumption, reaching the 2-point window band if the required opening sizes and locations comply. The rating-system paragraph does not explicitly resolve weighting for unequal-size spaces, so confirm that calculation basis before applying this example to such a project.1

Requirements

NC-only options address an episodic outdoor-event mode under ASHRAE Guideline 44 or an infection-risk mode under ASHRAE 241-2023, with design and commissioning verification. Thermal-safety paths use thermal modeling, or Passive House certification for the extreme-cold path, to show passive habitable conditions during a two-day peak-summer or peak-winter outage, and designate safety zones. Operable windows must meet the ASHRAE opening-size/location rules and cover the stated share of regularly occupied spaces.1

FAQ

Can Core and Shell claim the two management-mode options?

Those options are expressly limited to New Construction. Use the applicable thermal-safety or operable-window provisions for C&S.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 BD+C Rating SystemJuly 2026 · EQc4, printed pp. 165-166
  2. USGBC LEED credit library: Resilient Spaces: Exemplary Performance (EP20)Published Apr 22, 2025; retrieved November 8, 2026 · EP20 requirements

Maintained by VERTIQ, LEED software for consultants.