EQc4 Resilient Spaces
Protect occupants during adverse outdoor air, respiratory-disease events, extreme weather outages, or loss of mechanical ventilation through the eligible resilience paths.1
- Points
- See below
Reviewed · Spot an error? Report it
Points
NC and Core and Shell maximum 2 points. Each NC management-mode option earns 1. Summer and winter thermal-safety paths each earn 1. Operable windows earn 1 at 50% or 2 at 75% of regularly occupied spaces.1
Exemplary performance: achieving any additional option earns 1 exemplary performance point, claimed under Project Priorities (EP20).2
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Resilience management-mode sequences and commissioning verification
- Two-day thermal-outage model (or Passive House certification for the cold path) and thermal-safety-zone plans for selected heat/cold paths
- Regularly occupied space register, operable-window schedule and coverage calculation, and ASHRAE 62.1 opening-area and distance calculations
Worked example
Assume 20 equal-size regularly occupied spaces, and 15 have qualifying operable windows. Coverage is 15/20 × 100 = 75% both by space count and by area under this example assumption, reaching the 2-point window band if the required opening sizes and locations comply. The rating-system paragraph does not explicitly resolve weighting for unequal-size spaces, so confirm that calculation basis before applying this example to such a project.1
Requirements
NC-only options address an episodic outdoor-event mode under ASHRAE Guideline 44 or an infection-risk mode under ASHRAE 241-2023, with design and commissioning verification. Thermal-safety paths use thermal modeling, or Passive House certification for the extreme-cold path, to show passive habitable conditions during a two-day peak-summer or peak-winter outage, and designate safety zones. Operable windows must meet the ASHRAE opening-size/location rules and cover the stated share of regularly occupied spaces.1
FAQ
Can Core and Shell claim the two management-mode options?
Those options are expressly limited to New Construction. Use the applicable thermal-safety or operable-window provisions for C&S.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.