Credit Thermal Comfort
Meet both thermal design and occupant-control requirements.1
Reviewed · Spot an error? Report it
Points
1 point when both design and control components are met.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Thermal design calculations/standard-selection record.
- Preparation checklist: Space-by-space control schedule and plans, with guest-room or Retail scope exclusions identified.
Worked example
Assume 40 CI individual occupant spaces, 22 with qualifying controls. The fraction is 22/40=55%, above 50%. All shared multioccupant spaces still require group controls, and the design-standard checks remain separate.1
Requirements
Design HVAC and envelope to ASHRAE 55-2010 with errata/local equivalent, or the stated ISO 7730:2005 and EN 15251:2007 route. Natatoriums have a separate ASHRAE application reference.1
Provide individual controls for at least 50% of individual occupant spaces and group controls for every shared multioccupant space. A control adjusts at least one of temperature, radiant temperature, air speed or humidity. Exclude Hospitality guest rooms as stated; Retail applies the individual-space requirement in office/administrative areas.1
FAQ
Do controls alone earn the credit?
No. The credit requires thermal comfort design as well as controls.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 for Interior Design and ConstructionUpdated July 25, 2019 · Thermal Comfort; printed and PDF pp. 66-67