Credit Thermal Comfort
Meet thermal-comfort design criteria and provide the required occupant controls.1
Reviewed · Spot an error? Report it
Points
1 point. Both design and controls are required; Core and Shell is not listed for this credit in this edition.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Thermal comfort design report and assumptions
- HVAC/envelope specifications
- Individual/shared occupant-space schedule
- Control zoning and setpoint/control-function diagrams
Worked example
Assume a standard office has 100 individual occupant spaces and 10 shared spaces. At least 50 individual spaces need qualifying controls, and all 10 shared spaces need group controls. The control count does not independently establish thermal-design compliance.1
Requirements
Satisfy the cited ASHRAE 55-2010 or ISO/CEN design route, with the adaptation-specific treatment of warehouses, Data Centers and other special spaces. Standard control coverage requires at least 50% of individual occupant spaces and every shared multioccupant space. Healthcare requires controls for every patient room plus the remaining stated coverage; Hospitality guest rooms have a specific exclusion.1
FAQ
Must a control change air temperature specifically?
The source permits adjustment of at least one listed local comfort variable, including temperature, air speed, radiant temperature or humidity.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Thermal Comfort, printed/PDF pp. 127-128