Credit Thermal Comfort

Meet both thermal-comfort design and occupant-control requirements for the ID+C adaptation.1

Points
1 point
Applies to
ID+CBD+C
Other versions
v4
VERTIQ reference ID
EQc5

Reviewed · Spot an error? Report it

Points

1 point. Both design and control requirements must be met.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Thermal-comfort design analysis with conditions, system scope and standard/errata.
  • Preparation checklist: Individual/shared-space control schedule, count calculation and Hospitality guest-room exclusions where applicable.
  • Preparation checklist: Documentation that conditioned spaces meet ASHRAE 55-2017 for 80% acceptability, and an explanation of how the project complies with its direct solar radiation requirements.

Worked example

Assume a Commercial Interiors project has 40 individual occupant spaces and 22 with qualifying controls, and every shared multioccupant space has group controls. Individual coverage = 22 / 40 x 100 = 55%, above 50%. The project still needs documented comfort-design compliance; control coverage alone does not earn the point.1

Requirements

Design HVAC systems and the enclosure to ASHRAE 55-2017 with errata or a local equivalent. Natatoriums use the specified ASHRAE HVAC Applications Handbook natatorium design conditions.1

Provide individual thermal controls for at least 50% of individual occupant spaces and group controls for all shared multioccupant spaces. Controls adjust at least one of air temperature, radiant temperature, air speed or humidity. Hospitality guest rooms are assumed to have adequate controls and excluded from calculations. Retail applies the stated individual-space requirements to office and administrative areas.1

FAQ

Does a wall thermostat automatically prove thermal-comfort design?

No. The credit requires both compliant design and controls.1

Are Hospitality guest rooms included in the control denominator?

No. The Guide assumes adequate guest-room controls and excludes those rooms from the calculation.1