Credit Enhanced Indoor Air Quality Strategies
Apply the enhanced IAQ package for the ventilation mode and a qualifying additional strategy if pursued.1
Reviewed · Spot an error? Report it
Points
Option 1: 1 point. Option 2: 1 for CI/Hospitality or 2 for Retail. Maximum 2 for CI/Hospitality and 3 for Retail.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Entry/filter/exhaust plans and ventilation-mode scope matrix.
- Preparation checklist: Selected additional-strategy calculations, monitoring/control sequence or pollutant modeling.
Worked example
Assume mechanically ventilated occupied spaces each need a 1,000 cfm breathing-zone minimum. The increased-ventilation strategy needs at least 1,000 x 1.30 = 1,300 cfm for every applicable space. That strategy does not replace the Option 1 entry, contamination and filter requirements if those points are sought.1
Requirements
Option 1 requires entryway systems for all ventilation modes. Mechanically ventilated spaces also need contamination prevention and filtration; naturally ventilated spaces need natural-design calculations; mixed-mode spaces need all of those plus mixed-mode calculations. Entry systems are at least 10 feet (3 meters) long and maintained weekly. Applicable outdoor-air systems use MERV 13 or the stated equivalent and new media before occupancy. Projects in Japan may use ePM1 49% under JIS B 9908:2018 as the alternative to MERV 13.12
Option 2 selects an eligible additional strategy for each mode: exterior pollutant modeling, increased ventilation, source control/monitoring, or natural airflow calculations; CO2 monitoring is also listed for mechanically ventilated dense spaces. Increased breathing-zone ventilation is at least 30% above the prerequisite minimum.1
FAQ
Is one strategy interchangeable across every ventilation mode?
No. Select from the strategies explicitly allowed for the applicable mechanical, natural or mixed-mode spaces.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 for Interior Design and ConstructionUpdated July 25, 2019 · Enhanced Indoor Air Quality Strategies; printed and PDF pp. 55-57
- LEED v4 Reference Guide for Interior Design and Construction AddendaCumulative through February 20, 2026 · PDF p.51, April 10, 2020 Japan JIS filter entry
Maintained by VERTIQ, LEED software for consultants.