Credit Enhanced Indoor Air Quality Strategies

Implement multiple qualifying indoor-air-quality strategies. Retail receives a different upper score from Commercial Interiors and Hospitality.1

Points
See below
Applies to
ID+CBD+C
Other versions
v4
VERTIQ reference ID
EQc1

Reviewed · Spot an error? Report it

Points

Three compliant strategies: 1 point. Six: 2 points for Commercial Interiors/Hospitality or 3 points for Retail. Eight compliant strategies may support exemplary performance.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Selected-strategy matrix with locations, applicable systems, drawings and specifications.
  • Preparation checklist: Entryway maintenance, filtration, ventilation calculations and selected contaminant-monitoring/handling records.

Worked example

Assume a fit-out fully documents compliant entryway systems, interior cross-contamination prevention and outdoor-air filtration. Those are three distinct strategies, supporting 1 point. Installing six filters is not six strategies; count the credit strategy types and verify each entire applicable scope.1

Requirements

Choose from entryway systems, cross-contamination prevention, outdoor-air filtration, recirculated-air filtration, 15% increased ventilation, 30% increased ventilation, operable windows, engineered natural ventilation, CO2 monitoring, and additional source control/monitoring. Each selected strategy must satisfy its scope rather than merely appear in the design narrative.1

Entryway systems are at least 10 ft long in the travel direction and maintained weekly. Apply the exterior-entry boundary rule; projects without in-scope exterior entrances may use base-building evidence for the strategy. Cross-contamination spaces need the specified exhaust/negative-pressure and enclosure/door provisions. Both air-filtration strategies use MERV 13 or the stated ISO ePM1 50% alternative, with replacement before occupancy.12

The increased-ventilation strategies require at least 15% or 30% above the prerequisite breathing-zone rate in 95% of occupied spaces. Natural ventilation may use these strategies when documented consistently with the prerequisite and ASHRAE 62.1-2016 addendum l. Operable windows must serve at least 75% of regularly occupied spaces and meet the stated size/location rules. Engineered natural ventilation uses the prerequisite engineered path. CO2/source monitoring must meet their stated locations, setpoints and alarms.12

CO2 monitoring covers all densely occupied spaces, with monitors 3-6 ft above the floor and an alert above the calculated setpoint by more than 10%. Additional source control evaluates likely non-CO2 contaminants, implements a materials-handling plan and uses contaminant-specific sensors with alarms for unusual or unsafe conditions.1

FAQ

Can a tenant without exterior entrances use the entryway strategy?

The Guide/addendum permits base-building documentation where no exterior entrances are within the project scope.12

Does increased ventilation apply only to mechanical systems?

No. The Guide/addendum permits qualifying natural ventilation with the stated prerequisite-consistent documentation.12