Credit Enhanced Indoor Air Quality Strategies
Implement multiple qualifying indoor-air-quality strategies. Retail receives a different upper score from Commercial Interiors and Hospitality.1
Reviewed · Spot an error? Report it
Points
Three compliant strategies: 1 point. Six: 2 points for Commercial Interiors/Hospitality or 3 points for Retail. Eight compliant strategies may support exemplary performance.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Selected-strategy matrix with locations, applicable systems, drawings and specifications.
- Preparation checklist: Entryway maintenance, filtration, ventilation calculations and selected contaminant-monitoring/handling records.
Worked example
Assume a fit-out fully documents compliant entryway systems, interior cross-contamination prevention and outdoor-air filtration. Those are three distinct strategies, supporting 1 point. Installing six filters is not six strategies; count the credit strategy types and verify each entire applicable scope.1
Requirements
Choose from entryway systems, cross-contamination prevention, outdoor-air filtration, recirculated-air filtration, 15% increased ventilation, 30% increased ventilation, operable windows, engineered natural ventilation, CO2 monitoring, and additional source control/monitoring. Each selected strategy must satisfy its scope rather than merely appear in the design narrative.1
Entryway systems are at least 10 ft long in the travel direction and maintained weekly. Apply the exterior-entry boundary rule; projects without in-scope exterior entrances may use base-building evidence for the strategy. Cross-contamination spaces need the specified exhaust/negative-pressure and enclosure/door provisions. Both air-filtration strategies use MERV 13 or the stated ISO ePM1 50% alternative, with replacement before occupancy.12
The increased-ventilation strategies require at least 15% or 30% above the prerequisite breathing-zone rate in 95% of occupied spaces. Natural ventilation may use these strategies when documented consistently with the prerequisite and ASHRAE 62.1-2016 addendum l. Operable windows must serve at least 75% of regularly occupied spaces and meet the stated size/location rules. Engineered natural ventilation uses the prerequisite engineered path. CO2/source monitoring must meet their stated locations, setpoints and alarms.12
CO2 monitoring covers all densely occupied spaces, with monitors 3-6 ft above the floor and an alert above the calculated setpoint by more than 10%. Additional source control evaluates likely non-CO2 contaminants, implements a materials-handling plan and uses contaminant-specific sensors with alarms for unusual or unsafe conditions.1
FAQ
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 Interior Design and Construction GuideNovember 2025 · Enhanced Indoor Air Quality Strategies, printed/PDF pp. 146-150; ID+C scorecard printed/PDF pp. 5-6
- LEED ID+C v4.1 Addenda Table, first editionNovember 3, 2025 cumulative table · November 3, 2025 EQ Enhanced IAQ Strategies rows, Guide p148, entryway and increased natural ventilation; cumulative addenda PDF page 119
Maintained by VERTIQ, LEED software for consultants.