Credit Enhanced Indoor Air Quality Strategies

Reduce contaminant entry and exposure with ventilation-specific IAQ strategies.1

Points
Up to 2
Applies to
BD+CID+C
Other versions
v4.1
VERTIQ reference ID
EQc1

Reviewed · Spot an error? Report it

Points

Up to 2 points: 1 for each option's complete applicable requirements.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Entryway-system layouts
  • Exhaust/isolation and pressure design
  • Filter specifications and replacement records
  • Ventilation calculation and selected additional-strategy evidence

Worked example

Assume the calculated minimum breathing-zone outdoor air is 1,000 L/s. The increased-ventilation strategy requires at least 1,000 x 1.30 = 1,300 L/s for the applicable occupied spaces. One compliant zone does not establish whole-project coverage.1

Requirements

Option 1 applies entryway capture, cross-contamination control, filtration and/or natural/mixed-mode design calculations according to ventilation type. Mechanically ventilated supply uses the specified MERV 13 or F7-equivalent filtration and replacement timing. Option 2 adds an eligible strategy such as increased ventilation, exterior source protection or monitoring; the choices vary by ventilation type.1

FAQ

Can one entryway mat alone earn Option 1?

No. Apply all required strategies for each applicable ventilation type and space.1