Credit Enhanced Indoor Air Quality Strategies
Reduce contaminant entry and exposure with ventilation-specific IAQ strategies.1
Reviewed · Spot an error? Report it
Points
Up to 2 points: 1 for each option's complete applicable requirements.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Entryway-system layouts
- Exhaust/isolation and pressure design
- Filter specifications and replacement records
- Ventilation calculation and selected additional-strategy evidence
Worked example
Assume the calculated minimum breathing-zone outdoor air is 1,000 L/s. The increased-ventilation strategy requires at least 1,000 x 1.30 = 1,300 L/s for the applicable occupied spaces. One compliant zone does not establish whole-project coverage.1
Requirements
Option 1 applies entryway capture, cross-contamination control, filtration and/or natural/mixed-mode design calculations according to ventilation type. Mechanically ventilated supply uses the specified MERV 13 or F7-equivalent filtration and replacement timing. Option 2 adds an eligible strategy such as increased ventilation, exterior source protection or monitoring; the choices vary by ventilation type.1
FAQ
Can one entryway mat alone earn Option 1?
No. Apply all required strategies for each applicable ventilation type and space.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Enhanced Indoor Air Quality Strategies, printed/PDF pp. 114-116