Prerequisite Indoor Water Use Reduction
Reduce aggregate fixture water use by at least 20% and satisfy the applicable appliance and process-water requirements.1
Reviewed · Spot an error? Report it
Points
Required prerequisite; no points.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Plumbing fixture schedule with flow/flush rates and test pressure
- Product cutsheets, manufacturers' information, or a plumbing fixture schedule showing manufacturer, model, flush or flow rate and WaterSense or local-equivalent designation
- Occupancy and use schedule
- Kitchen, laundry and cooling-equipment schedules
Worked example
Assume the applicable baseline is 100,000 liters/year and design use is 78,000 liters/year. Reduction = (100,000 - 78,000) / 100,000 x 100 = 22%. This exceeds the 20% fixture threshold; labels, appliances and process conditions remain separate checks.1
Requirements
Base fixture calculations on the Table 1 volumes and flow rates, using the population inputs in the official calculator. Newly installed eligible toilets, urinals, private lavatory faucets and showerheads need WaterSense labeling, or a local equivalent outside the U.S.12
Tables 2-3 also govern appliances and processes. Healthcare, Retail, Schools and Hospitality have additional Tables 4-5. A fixture-only percentage is not the entire prerequisite.1
FAQ
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.