Prerequisite Indoor Water Use Reduction

Reduce calculated fixture and fitting consumption by at least 20% and comply with the applicable appliance and process-water requirements.1

Points
Required
Applies to
BD+CID+C
Other versions
v4
VERTIQ reference ID
WEp2

Reviewed · Spot an error? Report it

Points

Required prerequisite; no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Plumbing fixture schedule with flow and flush rates
  • WaterSense certificates or local-equivalent documentation
  • Completed indoor water use calculator with occupant groups
  • Appliance and cooling-equipment schedule with product data

Worked example

Assume a complete fixture calculation gives baseline use of 100,000 gallons/year and design use of 78,000 gallons/year. Reduction = (100,000 - 78,000)/100,000 x 100 = 22%, exceeding 20%. This addresses fixture savings only; labeling, appliance and process requirements still need review.1

For an illustrative 50% male/50% female group with all male urinal use, v05.1 gives equal low/full weighting. A 1.0/1.6 gpf dual-flush toilet therefore calculates to (1.0 + 1.6)/2 = 1.30 gpf for that group. Change the assumptions and recalculate; this is not a universal fixture rating.2

Requirements

Calculate aggregate fixture consumption using Table 1 baselines, occupant groups and use assumptions. Newly installed eligible toilets, urinals, private lavatory faucets and showerheads must have WaterSense labeling or a local equivalent outside the United States. A favorable aggregate result does not waive appliance or process requirements.1

Table 1 includes a 1.6 gpf toilet baseline, 1.0 gpf urinal baseline, 0.5 gpm public lavatory faucet baseline, 2.2 gpm private lavatory and kitchen faucet baselines, and 2.5 gpm shower baseline, at the stated supply pressures. Equipment requirements include avoiding potable once-through cooling and the specified cooling-tower controls. Apply additional kitchen and medical/process requirements where relevant.1

For dual-flush toilets, use the v05.1 calculator's occupant and urinal assumptions. Its weighted rate changes with the occupant split and male urinal use; do not replace the formula with a universal two-low-to-one-full rule.2

FAQ

Is a 20% fixture reduction enough by itself?

No. Eligible product labeling and applicable appliance and process-water requirements are also required.1

Can every dual-flush fixture use the same low/full weighting?

No. In calculator v05.1 the group weighting depends on occupant shares and male urinal use. Keep those inputs with the result.2

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 53-55
  2. USGBC LEED v4/v4.1 Indoor Water Use Reduction Calculatorv05.1 · Group 1, E25 dual-flush equation; K12/K13 occupant shares and I16 male urinal use

Maintained by VERTIQ, LEED software for consultants.