Credit Indoor Water Use Reduction

Earn points by reducing indoor fixture use beyond the prerequisite baseline, with additional equipment opportunities for certain adaptations.1

Points
See below
Applies to
BD+CID+C
Other versions
v4.1
VERTIQ reference ID
WEc2

Reviewed · Spot an error? Report it

Points

New Construction, Core and Shell, Data Centers, Warehouses and Hospitality: up to 6 points. Schools, Retail and Healthcare: up to 7. Hospitality can add one equipment-table point; Schools, Retail and Healthcare can add two.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Completed indoor water-use calculation
  • Plumbing schedule, or product cut sheets and manufacturer information
  • Population, operating-day and fixture-use assumptions
  • Alternative-water balance and equipment specifications where claimed

Worked example

Assume a New Construction baseline of 100,000 liters/year and proposed potable use of 60,000 liters/year, calculated with matching occupancy and fixture use. Reduction = 40%, earning 4 fixture points if the Indoor Water Use Reduction prerequisite and the remaining credit conditions are met.1

Requirements

Use the Indoor Water Use Reduction prerequisite baseline and include the fixtures needed by project occupants, including relevant fixtures outside the boundary. Alternative water sources can provide additional potable-water savings.1

For the general BD+C fixture path, reductions of 25%, 30%, 35%, 40%, 45% and 50% earn 1-6 points. For Schools, Retail, Hospitality and Healthcare, the fixture table stops at 45% for 5 points; qualifying appliance/process tables can add points within the adaptation's cap.1

FAQ

Does passing the Indoor Water Use Reduction prerequisite automatically earn this credit?

No. A 20% fixture reduction satisfies the prerequisite threshold, while the first credit point starts at 25%.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Indoor Water Use Reduction, printed/PDF pp. 56-58; WE Prerequisite Indoor Water Use Reduction, printed/PDF p. 51

Maintained by VERTIQ, LEED software for consultants.