Credit Light Pollution Reduction
Control exterior uplight, light trespass and internally illuminated signage.1
- Points
- 1 point
- Applies to
- BD+C
- VERTIQ reference ID
- SSc6
Reviewed · Spot an error? Report it
Points
1 point.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Exterior luminaire schedule and IES photometric files
- Lighting-zone and boundary plan
- BUG-rating or illuminance calculation report
- Signage luminance specifications
Worked example
Assume three exterior fixtures are tested but a fourth nonexempt luminaire is omitted. Coverage = 3 / 4 = 75%, which does not establish this whole-project credit. Include every nonexempt fixture in the relevant method.1
Requirements
Select the correct MLO lighting zone and demonstrate uplight and trespass compliance using the BUG or calculation method; the methods can differ between those two topics. Assess installed luminaire orientation and tilt, the applicable lighting boundary and listed exemptions. Address internally illuminated signage separately.1
FAQ
Does an efficient LED automatically comply?
No. The requirements depend on distribution, orientation, zone, trespass and signage, not only energy efficiency.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Light Pollution Reduction, printed/PDF pp. 40-43
Maintained by VERTIQ, LEED software for consultants.