Credit Interior Lighting

Provide occupant lighting control and/or a qualifying combination of lighting-quality strategies.1

Points
See below
Applies to
BD+CID+C
Other versions
v4.1
VERTIQ reference ID
EQc6

Reviewed · Spot an error? Report it

Points

Up to 2 points for the standard paths, 2 for Retail and 1 for Healthcare. Core and Shell is not listed in this edition.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Luminaire and control schedule
  • Individual/shared-space plan
  • Lighting calculations and photometric/product data
  • Selected quality-strategy calculation sheets

Worked example

Assume 100 standard individual occupant spaces and 92 have compliant controls. Coverage = 92%, exceeding the 90% individual-space threshold. All shared spaces and the other control requirements must still comply.1

Requirements

The standard control option covers at least 90% of individual spaces and all shared spaces, with the required scenes/levels, multizone controls and presentation-wall treatment. The standard lighting-quality option chooses four of the listed strategies with their scope and thresholds. Retail and Healthcare have distinct provisions; Hospitality guest-room treatment also differs.1

FAQ

Do on/off switches satisfy the standard three-level control requirement?

No. The standard control path calls for on, off and a midlevel scene, along with the other applicable provisions.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Interior Lighting, printed/PDF pp. 129-130