Credit Interior Lighting
Provide occupant lighting control and/or a qualifying combination of lighting-quality strategies.1
Reviewed · Spot an error? Report it
Points
Up to 2 points for the standard paths, 2 for Retail and 1 for Healthcare. Core and Shell is not listed in this edition.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Luminaire and control schedule
- Individual/shared-space plan
- Lighting calculations and photometric/product data
- Selected quality-strategy calculation sheets
Worked example
Assume 100 standard individual occupant spaces and 92 have compliant controls. Coverage = 92%, exceeding the 90% individual-space threshold. All shared spaces and the other control requirements must still comply.1
Requirements
The standard control option covers at least 90% of individual spaces and all shared spaces, with the required scenes/levels, multizone controls and presentation-wall treatment. The standard lighting-quality option chooses four of the listed strategies with their scope and thresholds. Retail and Healthcare have distinct provisions; Hospitality guest-room treatment also differs.1
FAQ
Do on/off switches satisfy the standard three-level control requirement?
No. The standard control path calls for on, off and a midlevel scene, along with the other applicable provisions.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Interior Lighting, printed/PDF pp. 129-130