Prerequisite Minimum Energy Performance
For LEED v4 BD+C projects registered on or after March 1, 2024, the updated whole-building simulation path requires 10% improvement for standard New Construction, 8% for Core and Shell and Data Centers, and 5% for Healthcare.1
Reviewed · Spot an error? Report it
Points
Minimum Energy Performance is a prerequisite and awards no points. The separate updated Optimize Energy Performance credit adds points from its cost/source-energy table and GHG table; passing the prerequisite alone does not earn those credit points.12
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Project registration record and adaptation confirming whether the 2024 Energy Update applies.
- Energy model report documenting ASHRAE 90.1-2010 Appendix G, baseline/proposed values and the chosen metric.
- Building drawings, equipment schedules and calculation notes supporting mandatory provisions, unregulated loads and any claimed threshold exception.
Worked example
Illustrative standard New Construction, energy-cost metric: baseline annual cost = 100,000 monetary units; proposed annual cost = 89,000. Improvement = (100,000 - 89,000) / 100,000 × 100 = 11%, above the updated 10% minimum. This example assumes neither threshold exception applies and does not replace mandatory-provision or model checks.1
Requirements
Scope: this page covers the BD+C 2024 Energy Update, Option 1, and summarizes the original criteria for earlier registrations; confirm the registration date and applicable adaptation before using its thresholds.1
The simulation reference remains ASHRAE 90.1-2010 Appendix G with errata; the updated improvement metric can be energy cost, source energy or GHG emissions.1
New Construction, major renovations, Schools, Warehouses and Distribution Centers, and Hospitality require at least 10%; Core and Shell and Data Centers require 8%; Healthcare requires 5%.1
The published exceptions permit the Core and Shell column for projects with unregulated energy exceeding 50% of proposed performance in the selected metric or restaurant area exceeding 40%; Core and Shell healthcare may use the Healthcare criteria.1
Mandatory provisions and unregulated-load documentation still apply; new off-site or community renewables cannot be deducted to satisfy the prerequisite.1
Original criteria for registrations before March 1, 2024: Option 1 requires 5% improvement for new construction, 3% for major renovations or 2% for core and shell against ASHRAE 90.1-2010 Appendix G, before taking credit for renewable energy. Data Centers require 5%, with separate building and IT models and at least 2% from building power and cooling infrastructure. Option 2 follows the ASHRAE 50% Advanced Energy Design Guide. Option 3 follows the Advanced Buildings Core Performance Guide for projects under 100,000 square feet (9,290 square meters), excluding healthcare, warehouse and laboratory projects.3
FAQ
Does the 2024 update change the reference standard to 90.1-2016?
The updated v4 Option 1 described here retains ASHRAE 90.1-2010 Appendix G with errata; separate v4.1 alternatives require their own pathway checks.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- USGBC: Minimum Energy Performance, BD+C v4 2024 update2024 Energy Update, verified October 21, 2026 · ea403/2024update, Option 1 and applicability/renewable-energy notes
- USGBC: Optimize Energy Performance, BD+C v4 2024 updateOfficial language captured October 23, 2026 · ea404/2024update, Tables 1-2 and renewable-energy notes
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Minimum Energy Performance, printed/PDF pp. 65-67