Credit Indoor Water Use Reduction
Earn ID+C water points by reducing fixture and fitting demand beyond the prerequisite baseline. Retail and Hospitality may add points for qualifying appliance and process improvements, within the 12-point credit cap.1
Reviewed · Spot an error? Report it
Points
2-12 points. Commercial Interiors fixture maximum: 12. Retail: up to 10 fixture points plus 2 equipment points. Hospitality: up to 11 fixture points plus 1 equipment point. Total maximum: 12.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Indoor water use calculator including all occupant-serving fixtures; product cutsheets, manufacturers' information or plumbing schedules; alternative water calculations, plumbing drawings and narrative where used.
- Preparation checklist: For equipment points, adaptation and table eligibility, equipment ratings, annual laundry or daily meal data and process compliance records.
Worked example
Assume a Commercial Interiors project has baseline fixture demand of 100,000 gallons/year and design demand of 60,000 gallons/year. Reduction = (100,000 - 60,000) / 100,000 x 100 = 40%, worth 8 fixture points. The same 40% fixture tier is worth 8 points for Retail and Hospitality, before any separately demonstrated equipment point.1
Requirements
Include the fixtures and fittings needed by project occupants, even when some are outside the tenant space. Calculate demand reduction from the Indoor Water Use Reduction prerequisite baseline with consistent use assumptions; alternative water sources may provide additional potable-water savings.1
Fixture reductions of 25%, 30%, 35%, 40% and 45% earn 2, 4, 6, 8 and 10 points for all three adaptations. At 50%, Commercial Interiors earns 12 fixture points, Hospitality earns 11, and Retail has no additional fixture tier above 10.1
Retail and Hospitality must meet the fixture reduction requirements before adding appliance/process points. One point is available for meeting all applicable requirements of one of Tables 2 through 5. Retail can earn a second point for a second table; Hospitality can add one point. Table eligibility includes at least 120,000 pounds/year of laundry for Table 2, at least 100 meals/day for Table 3, a medical/laboratory facility for Table 4, or a qualifying non-return municipal/district steam connection for Table 5.1
FAQ
Can 50% fixture savings alone earn 12 points in Retail?
No. The Retail fixture table stops at 10 points. The additional two points require qualifying appliance/process tables.1
Does every kitchen earn an equipment point?
No. Table 3 requires at least 100 meals per day of operation and compliance by all installed equipment in each applicable kitchen-equipment category.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 Interior Design and Construction GuideNovember 2025 · Indoor Water Use Reduction, printed/PDF pp. 33-36; ID+C scorecard printed/PDF pp. 5-6
Maintained by VERTIQ, LEED software for consultants.