Credit Daylight
Provide glare control and demonstrate daylight through one of the ID+C simulation or measurement options, using regularly occupied floor area.1
Reviewed · Spot an error? Report it
Points
1-3 points under the selected option. Do not sum simulation and measurement option scores.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Regularly occupied area and glare-control schedule with furniture/obstruction inputs.
- Preparation checklist: Selected option simulation files and sDA/ASE or illuminance outputs, or field measurements with grids, dates and qualifying-area calculations.
Worked example
Assume Option 1 has two regularly occupied areas: 600 m2 at sDA 60% and 400 m2 at sDA 50%. Area-weighted result = (600 x 0.60 + 400 x 0.50) / 1,000 x 100 = 56%, earning 2 points. The 400 m2 area is below 55%, so this example does not claim the every-space bonus. Assume all glare, ASE reporting and model conditions are met.1
Requirements
Provide manual glare control or automatic control with manual override for all regularly occupied spaces. Select one option and include permanent interior obstructions, movable furniture and partitions as specified. Nordic projects should check the Daylight for Nordic Projects regional alternative compliance path.12
Option 1 uses annual IES LM-83-12 sDA300/50% and ASE1000,250 analysis for each regularly occupied space, with the specified grid, work-plane and weather inputs. Average floor-area sDA of at least 40/55/75% earns 1/2/3 points. For each space with ASE above 10%, identify its glare response; ASE above 10% is not an automatic failure. Meeting sDA at least 55% in every regularly occupied space earns exemplary performance, or 1 additional point if 2 points are achieved above.1
Option 2 simulates equinox illuminance at 9 a.m. and 3 p.m.; 55/75/90% qualifying area earns 1/2/3 points. Normally illuminance must be 300-3,000 lux; the specified view-preserving automatic/manual-override glare devices permit the minimum-only route. Option 3 measures qualifying illuminance after furniture/fixtures/equipment are installed: 55% at one time earns 1 point, 75% at two times earns 2, and 90% at two times earns 3. Follow the measurement grid and Table 4 seasonal timing.1
FAQ
Must every room have ASE at or below 10% to earn points?
The Guide requires identifying the glare design response for spaces above 10%, along with the universal glare-control requirement.1
Can equally averaging unequal rooms establish the floor-area result?
Use the total regularly occupied floor area result. The example weights each area rather than taking an unweighted mean of room percentages.1