Credit Indoor Air Quality Assessment

After finishes are installed and the project is cleaned, choose the flush-out option or the air-testing option. Their points cannot be combined.1

Points
See below
Applies to
ID+CBD+C
Other versions
v4
VERTIQ reference ID
EQc4

Reviewed · Spot an error? Report it

Points

Option 1 flush-out: 1 point. Option 2: 1 point per compliant testing path, maximum 2. Flush-out and testing cannot combine.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Completion/cleaning/filter records and the selected assessment plan.
  • Preparation checklist: Measured outdoor-air volume and environmental logs for the flush-out report, or the IAQ testing report with accredited laboratory results, ISO/IEC 17025 certificate and accredited scope highlighting the test methods used, sample locations, methods, limits and corrective-action/retest records.

Worked example

Assume a 10,000 ft2 project uses the complete preoccupancy flush-out path with constant measured outdoor airflow of 10,000 cfm. Required volume = 10,000 x 14,000 = 140,000,000 ft3. Time = 140,000,000 / 10,000 = 14,000 minutes, or 233.33 hours. This assumes the required temperature/humidity, completion, cleaning and filter conditions throughout; it does not convert a total supply-air reading into outdoor airflow.1

Requirements

Complete construction, all interior finishes and movable furnishings, major VOC punch-list work and final cleaning before the assessment. Option 1 flush-out supplies 14,000 ft3 of outdoor air per ft2 of gross floor area, with new filters, temperature between 60 and 80 F and relative humidity no greater than 60%.1

The early-occupancy flush-out path permits occupancy after at least 3,500 ft3/ft2. Continue at the greater of 0.30 cfm/ft2 or the prerequisite design minimum, beginning at least three hours before occupancy each day and continuing during occupancy, until the total 14,000 ft3/ft2 is delivered. Maintain the stated environmental conditions.1

Option 2 tests under normal occupied ventilation conditions after construction and before occupancy; Retail may test within 14 days of occupancy. Path 1 particulate/inorganic-gas testing earns 1 point, Path 2 VOC testing earns 1, or both earn 2. Meet all applicable Table 1/2 limits and methods. The PM2.5 limit is 12 micrograms/m3, or 35 only in qualifying high-ambient/nonattainment areas. VOC testing includes the full individual-compound list and TVOC screening; TVOC above 500 micrograms/m3 triggers investigation/correction as required, rather than an automatic TVOC failure.1

FAQ

Can flush-out and one testing path add to two points?

No. The two options cannot be combined.1

Is 500 micrograms/m3 TVOC a simple pass/fail limit?

The Guide uses it as a screening trigger for investigating individual VOCs and correcting identified issues, not as an automatic credit failure.1