Prerequisite Minimum Energy Performance
Meet the ID+C fit-out energy standard using ASHRAE 90.1-2016 mandatory provisions and an eligible prescriptive, energy-cost-budget or Appendix G performance path.1
Reviewed · Spot an error? Report it
Points
Required prerequisite; 0 points. Optimize Energy Performance points require additional credit analysis and that credit's own scoring.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation checklist: Fit-out scope, standard/errata selection, mandatory-provision checklist and compliance drawings.
- Preparation checklist: Selected path evidence: ASHRAE 90.1-2016 compliance forms or COMcheck report with supporting construction drawings; ECB input-output reports, utility rates and compliance documentation; or Minimum Energy Performance Calculator with Appendix G inputs, input-output reports, end-use consumption and demand, utility rates or GHG calculations with emission factors, exceptional calculations and on-site renewable plans where applicable.
- Preparation checklist: For performance-path projects in Europe, calculated fenestration U-factors from LBNL Windows 6 or software approximating NFRC methods, or a narrative supporting the modeled value.
Worked example
Assume the Appendix G target PCIt is 0.80 and the proposed PCI is 0.75 for the selected prerequisite metric. PCI <= PCIt because 0.75 <= 0.80. Improvement relative to the target = (0.80 - 0.75) / 0.80 x 100 = 6.25%. This example checks the target arithmetic only; the model scope and mandatory provisions remain required.1
Requirements
Comply with ASHRAE 90.1-2016 with errata, or a USGBC-approved equivalent standard, including the applicable mandatory provisions together with the prescriptive provisions of Sections 5 through 10, Section 11 Energy Cost Budget, or Appendix G Performance Rating Method. Section 11 is available only to projects pursuing no Optimize Energy Performance points. Projects in Europe may use the Europe ACP for ASHRAE 90.1 Mandatory Provisions Table in lieu of certain mandatory provisions. Under Appendix G, demonstrate PCI no greater than PCIt using the applicable new-construction Building Performance Factors.1
For the Appendix G prerequisite, document compliance using energy cost or greenhouse gas emissions. The Guide allows qualifying on-site or on-campus renewable energy under Section G2.4.1 for minimum performance. Follow its explicit provisions for modeled mandatory controls and exceptional calculations rather than assuming all mandatory provisions can be waived.1
For prescriptive documentation, the current ID+C addenda identify system-by-system ASHRAE 90.1-2016 compliance forms or applicable COMcheck reports and the relevant project drawings.12
FAQ
Can off-site renewable purchases replace minimum tenant efficiency?
The prerequisite permits the specified on-site or on-campus renewable treatment. Do not apply the separate Optimize Energy Performance off-site GHG provision as a prerequisite efficiency substitute.1
Does this prerequisite use the BD+C minimum percentage table?
No. Apply the ID+C requirements and selected compliance path; the Appendix G test is PCI <= PCIt.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 Interior Design and Construction GuideNovember 2025 · Minimum Energy Performance prerequisite, printed/PDF pp. 40-71; ID+C scorecard printed/PDF pp. 5-6
- LEED ID+C v4.1 Addenda Table, first editionNovember 3, 2025 cumulative table · November 3, 2025 row for EA prerequisite Minimum Energy Performance, Guide p70 documentation table; cumulative addenda PDF page 39
Maintained by VERTIQ, LEED software for consultants.