Credit Optimize Energy Performance

Analyze tenant efficiency measures during design and earn ID+C points through a tenant-level performance model or the eligible prescriptive option. The modeled option adds separate energy-cost and greenhouse-gas scores.1

Points
See below
Applies to
ID+CBD+C
Other versions
v4
VERTIQ reference ID
EAc2

Reviewed · Spot an error? Report it

Points

Option 1 tenant model: 4-24 points. Option 2 prescriptive compliance: 1-17 points. Select an option; do not sum the two option totals.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation checklist: Design-phase efficiency options, estimated savings/cost impacts and decision record.
  • Preparation checklist: Tenant baseline/proposed energy model, PCI/PCIt cost and GHG calculations, factor/tariff and renewable provenance; or complete selected prescriptive strategy evidence.
  • Preparation checklist: Target Finder results and summary for Option 1, for applicable building types.

Worked example

Assume compliant Appendix G models establish a cost PCIt of 0.80 and cost PCI of 0.704, and a GHG PCIt of 0.90 and GHG PCI of 0.738. Cost improvement = (0.80 - 0.704) / 0.80 x 100 = 12%, worth 8 points. GHG improvement = (0.90 - 0.738) / 0.90 x 100 = 18%, worth 9 points. Total = 8 + 9 = 17 modeled points. This example assumes all model and prerequisite conditions are met.1

Requirements

During design, analyze load reduction, HVAC and passive measures, estimate savings and cost implications, and show how the analysis informed decisions. For Option 1, use the ASHRAE 90.1-2016 Appendix G tenant model and calculate PCI and PCIt for cost and GHG. For mixed-use projects, apply the specified area-weighted building-type approach.1

Option 1 cost thresholds for percent PCI below PCIt are 0%, 3%, 6%, 9%, 12%, 15%, 18%, 21% and 24%, worth 4 through 12 points. GHG thresholds are 0%, 3%, 6%, 9%, 12%, 18%, 25%, 35% and 50%, also worth 4 through 12. Add the two scores. The 0% rows are subject to the base-building-compliance footnote. Qualifying on-site/on-campus renewables may affect both metrics; eligible Tier 2 new off-site renewables affect only GHG, with hourly factors where available.1

Option 2 requires the prerequisite prescriptive path. AEDG envelope and lighting strategies also need the project space to meet the applicable AEDG scope, and AEDG HVAC strategies need the entire building to meet it. It provides up to 5 base-building points and 12 tenant-system points. Tenant lighting includes LPD reductions of 10/20/30/40/50% for 1-5 points and daylight-responsive controls serving 35/70% of connected lighting load for 1/2 points. Eligible equipment rated-power shares of 20/40/60/80/100% earn 1-5 points, with at least 0.25 W/ft2 of eligible equipment in the project scope.1

Retain confirmation of the design-phase efficiency analysis as identified in the November 2025 ID+C documentation addendum.12

FAQ

Is a single cost-saving percentage enough to establish the modeled total?

No. Option 1 totals the separate cost and GHG table scores, using each metric PCI and PCIt.1

Can off-site renewable purchases improve both modeled tables?

The specified Tier 2 new off-site renewable treatment applies to the GHG metric only. Follow the credit conditions and hourly methodology where available.1