Prerequisite Environmental Tobacco Smoke Control

Adopt and enforce a smoking policy with the required separation and residential controls.1

Points
Required
Applies to
BD+CID+C
Other versions
v4
VERTIQ reference ID
EQp2

Reviewed · Spot an error? Report it

Points

Required prerequisite; no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • No-smoking policy and enforcement/signage plan
  • Site map showing smoking areas, openings and intakes, plus the local code excerpt and narrative where a code limit replaces the 7.5 m distance
  • Residential compartmentalization test report if that path is used

Worked example

Assume a designated general-route smoking area is 5 m from an outdoor-air intake and 10 m from the entrance. The intake distance fails the stated 7.5 m separation even though the entrance distance passes; evaluate all three receptor types.1

Requirements

For the general route, prohibit indoor smoking and restrict outdoor smoking to designated locations at least 7.5 m from entries, intakes and operable windows, subject to the stated local-code limit. The definition includes electronic devices and combustion of cannabis/controlled substances. Communicate and enforce the policy or provide signage. Schools prohibit smoking on site. A residential smoking-unit alternative requires sealing and compartmentalization testing rather than a simple indoor-smoking exemption.1

FAQ

Are e-cigarettes excluded from the policy?

No. The prerequisite includes emissions from electronic smoking devices.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 114-115

Maintained by VERTIQ, LEED software for consultants.