WEp1 Minimum Water Efficiency

Meet one fixture-efficiency route and the applicable minimum efficiency rules for newly installed water-using equipment.1

Points
Required
Applies to
ID+CBD+C

Reviewed · Spot an error? Report it

Points

Required prerequisite; no points. Fixture compliance alone does not replace the applicable equipment and process requirements.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation: Fixture schedule including full-flush volumes and flow rates
  • Preparation: Baseline/proposed fixture calculation with occupancy and use assumptions
  • Preparation: New equipment schedule and water-efficiency specifications

Worked example

Assume the complete fixture calculation has a baseline of 100,000 gal/year and proposed use of 78,000 gal/year. Reduction = (100,000 - 78,000) / 100,000 x 100 = 22%, above the 20% threshold. A dual-flush toilet with a 1.6 gpf full flush still fails the separate 1.28 gpf full-flush limit, regardless of its weighted average.1

Requirements

Include all new and existing fixtures and fittings in the tenant space. Either meet the prescriptive maximums or achieve at least a 20% aggregate reduction from the fixture baseline. Local standard supply pressure may be used where it differs from the LEED baseline pressure.1

Prescriptive maximums are 1.28 gpf for toilets, 0.50 gpf for urinals, 0.50 gpm for public lavatory faucets, 1.50 gpm for private lavatory faucets, 1.8 gpm for kitchen faucets and 2.00 gpm for showerheads. For dual-flush toilets, the full flush must not exceed 1.28 gpf or 4.8 lpf; a weighted average cannot be used. This footnote also appears under the performance-path baseline table.1

New appliances, equipment and processes must meet Tables 3-4; existing appliances and equipment may be excluded. Requirements include applicable ENERGY STAR or performance-equivalent specifications, prerinse spray valves at no more than 1.3 gpm, no potable once-through cooling, controlled discharge-water tempering and no water-flow vacuum generators.1

FAQ

Can existing tenant fixtures be ignored?

No. Both fixture routes cover new and existing fixtures and fittings within the tenant space. Existing appliances and equipment may be excluded from the separate equipment requirement.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 ID+C Rating SystemJuly 2026 · WEp1; printed pp. 21-23, PDF pp. 26-28; scorecard printed pp. 1-2, PDF pp. 6-7

Maintained by VERTIQ, LEED software for consultants.