EQc1 Enhanced Air Quality
Exceed the prerequisite through increased ventilation or verified enhanced indoor-air-quality design. The available option depends on the procedure used in EQp2.1
Reviewed · Spot an error? Report it
Points
NC and Core and Shell: 1 point through either route. Thirty-percent increased ventilation is identified as exemplary performance, not a second ordinary point in this credit.1
Exemplary performance: increasing breathing zone outdoor air ventilation rates by at least 30% under Option 1 earns 1 exemplary performance point, claimed under Project Priorities (EP6).2
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- EQp2 ventilation-procedure selection and baseline rates
- Enhanced ventilation calculations and occupied-space coverage register
- Enhanced IAQ design and verification report for Option 2
- HVAC controls and airflow commissioning records
Worked example
Assume a minimum breathing-zone outdoor-air requirement of 1,000 L/s for the assessed spaces. A 15% increase is 1,000 × 1.15 = 1,150 L/s. Meeting that flow does not establish the point unless the required space coverage and other path conditions are met.1
Requirements
Projects using the Ventilation Rate Procedure can choose either option; those using the Indoor Air Quality Procedure use enhanced IAQ design. Increased ventilation provides at least 15% above minimum breathing-zone outdoor-air rates to 95% of regularly occupied spaces. Enhanced IAQ design adds lower limits for PM2.5, formaldehyde, and ozone to the specified ASHRAE design compounds/limits and verifies the design.1
FAQ
Can an IAQ Procedure project choose only the 15% airflow option?
The credit directs IAQ Procedure projects to Option 2, Enhanced Indoor Air Quality Design.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 BD+C Rating SystemJuly 2026 · EQc1, printed pp. 155-156
- USGBC LEED credit library: Enhanced Air Quality: Exemplary Performance (EP6)Published Apr 21, 2025; retrieved November 8, 2026 · EP6 requirements