EAp4 Energy Metering and Reporting
Monitor energy use and peak electrical demand and commit to reporting 12 months of monthly data at least annually.1
- Points
- Required
- Applies to
- BD+CID+C
Reviewed · Spot an error? Report it
Points
Required for NC and Core and Shell; no points. Annual reporting contains monthly data for 12 consecutive months.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Energy meter/device schedule and electrical/energy-system diagrams
- ASHRAE monitoring compliance matrix
- Monthly source-specific energy, renewable-generation, and peak-demand reporting template
- Owner annual-reporting commitment
Worked example
Assume the report contains January through December electricity and fuel totals plus peak demand and renewable output. That supplies 12 consecutive monthly records per required data stream. A single annual electricity total is not equivalent to those 12 monthly records.1
Requirements
Meet the applicable ASHRAE 90.1 monitoring provisions, using 2019 or later for registration before January 1, 2028, and 2022 or later afterward. Also monitor on-site renewable electricity. Major renovations and otherwise-excepted buildings still need devices for whole-building use by source and peak electrical demand at least monthly. Commit to USGBC reporting for five years or until ownership/lessee changes. Future tenant services/meters in tenant scope are excepted for Core and Shell.1
FAQ
Is an annual electricity bill total enough?
No. The reporting commitment includes monthly data for 12 consecutive months, each energy source, renewable generation, and peak electrical demand.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 BD+C Rating SystemJuly 2026 · EAp4, printed pp. 83-84
Maintained by VERTIQ, LEED software for consultants.