EAc4 Renewable Energy

Supply or procure qualifying renewable energy and document its tier, quantity, contract term, and environmental attributes. NC and Core and Shell use different energy denominators and point tables.1

Points
See below
Applies to
BD+CID+C
Other versions
v4.1

Reviewed · Spot an error? Report it

Points

Maximum 5 points for NC and 4 for Core and Shell. NC Tier 1 energy thresholds are 5%, 10%, 20%, and 35% for 1-4 points, and 1 or 2 Tier 1 points can instead use minimum rated capacity of A × 1 or A × 2 W/sq. ft. (A × 10.8 or A × 21.6 W/sq. m.), where A is the gross floor area of all floors up to the three largest floors; Tier 2 is 20%, 40%, 60%, and 80%; Tier 3 is 50%/100% for 1/2 points. Five NC points require 100% Tier 1 and/or Tier 2. Tier contributions can be combined within the cap. Platinum requires 100% qualifying site energy for NC or base-building energy for C&S from any combination of the three tiers, a separate condition from earning the maximum credit points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Annual site-energy model or utility-energy estimate with consistent energy units
  • Renewable system capacity and annual production report
  • Power or EAC/REC purchase agreement showing term, asset, location, and tier evidence
  • Environmental-attribute retirement records and certificate-vintage schedule
  • Core and Shell base-building denominator calculation or readiness drawings and tenant guidelines, as applicable

Worked example

Assume NC annual site energy of 1,000 MWh-equivalent and 100 MWh-equivalent of qualifying Tier 1 energy, with compliant attributes retained and retired. Coverage = 100/1,000 × 100 = 10%, reaching 2 points under the Tier 1 energy column. This does not meet the 100% renewable-energy condition for Platinum. The assumed quantities are annual energy, not installed power capacity.1

Requirements

Tier 1 covers qualifying on-site, campus, or social-impact generation; Tier 2 covers qualifying new off-site electricity; Tier 3 covers certified or equivalent off-site renewable electricity or renewable fuels. Retire the associated EACs/RECs on behalf of the project. Contracts are 10 years, with shorter terms prorated across 10 years. Apply energy-source matching, location, and certificate-vintage requirements.1

For Core and Shell, base-building site energy is the greater of estimated base-building meter consumption or 25% of total estimated building energy. A separate readiness option is available only to Core and Shell. It requires the specified solar-zone, structural, pathways, electrical-service, and tenant-guideline provisions, not simply spare roof space.1

FAQ

Can renewable electricity cover unrelated on-site fuel use?

No. Apply the source-matching restrictions. Renewable electricity and EACs address eligible electricity or district-energy use; renewable fuels address eligible fuel or district-heat use within the stated limits.1

Does selling the system's RECs still support the same LEED claim?

The environmental attributes must be retired on behalf of the LEED project to contribute. Generation alone does not establish that condition.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 BD+C Rating SystemJuly 2026 · EAc4, printed pp. 109-113