Prerequisite Building-Level Water Metering

Meter total potable water use for the building and associated grounds and summarize it over time.1

Points
Required
Applies to
BD+C
Other versions
v4.1
VERTIQ reference ID
WEp3

Reviewed · Spot an error? Report it

Points

Required prerequisite; no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Water service and meter diagram
  • Meter specifications and reading protocol
  • Monthly/annual reporting template
  • Data sharing confirmation
  • Meter declaration

Worked example

Assume monthly readings total 12,000 m3 across all project potable supply meters. The annual summary is the sum of those 12 monthly totals; an unmetered irrigation branch must be addressed before that total represents the whole project.1

Requirements

Install permanent meters covering total project potable use. Compile monthly and annual summaries; manual or automated readings are allowed. Commit to the source's five-year USGBC data-sharing period beginning at certification acceptance or typical occupancy, whichever is first, subject to the stated ownership/lessee condition.1

FAQ

Must every reading be automated?

No. Manual readings are allowed if the permanent-meter coverage and required summaries are provided.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Building-Level Water Metering prerequisite, printed/PDF pp. 54

Maintained by VERTIQ, LEED software for consultants.