Prerequisite Minimum Acoustic Performance
Provide acoustic conditions for classrooms and core learning spaces in Schools projects.1
- Points
- Required
- Applies to
- BD+C
- Other versions
- v4.1
- VERTIQ reference ID
- EQp3
Reviewed · Spot an error? Report it
Points
Required for Schools; no points.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Classroom volume and finish schedule
- HVAC noise analysis
- Exterior-noise study where needed
- NRC product data and reverberation calculations
Worked example
Assume a qualifying small classroom has 80 m2 ceiling area after the stated exclusions. If counted NRC-at-least-0.70 absorptive surfaces total 85 m2, area coverage = 85 / 80 = 106.25%, supporting that prescriptive surface-area check. Background and exterior noise remain separate.1
Requirements
Limit HVAC background noise to 40 dBA and address exterior noise under the source's conditions. For small classrooms/core learning rooms, use the prescriptive absorptive-area path or demonstrate compliant reverberation times by calculation; larger spaces use the cited speech-room guidance. Historic/scope exceptions require consideration rather than automatic exemption.1
FAQ
Does acoustic ceiling coverage alone satisfy the prerequisite?
No. HVAC noise, exterior-noise conditions and the applicable reverberation requirements must all be addressed.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4 BD+C Rating SystemUpdated July 25, 2019 · Minimum Acoustic Performance prerequisite, printed/PDF pp. 112-113