Prerequisite Minimum Acoustic Performance
Schools must control HVAC background noise, exterior noise and reverberation in core learning spaces.1
- Points
- Required
- Applies to
- BD+C
- Other versions
- v4
- VERTIQ reference ID
- EQp3
Reviewed · Spot an error? Report it
Points
Required for Schools; no points.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Classroom/core-learning space schedule
- HVAC acoustic design or test report
- Absorptive-finish area/NRC schedule or reverberation report
- Exterior noise assessment
Worked example
Assume a classroom has 80 m2 of ceiling area after the listed fixture exclusions. An absorptive finish route needs at least 80 m2 of qualifying surfaces with NRC at least 0.70. Providing 50 m2 of ceiling plus 30 m2 of wall treatment reaches that area test; HVAC and exterior noise still require review.1
Requirements
Schools only. Limit HVAC background noise in classrooms/core learning spaces to 40 dBA. Address exterior intrusion at high-noise sites, subject to the specified distance exemption. For reverberation, use the eligible absorptive-finish method, ANSI calculation/measurement method, or the large-volume room requirements as applicable. Historic/limited-scope exceptions are considered, while specialized acoustic spaces require professional attention and are outside this prerequisite's stated application.1
FAQ
Does a good reverberation result waive HVAC noise control?
No. The prerequisite addresses both, plus applicable exterior noise.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 116-117
Maintained by VERTIQ, LEED software for consultants.