Prerequisite Minimum Acoustic Performance

Schools must control HVAC background noise, exterior noise and reverberation in core learning spaces.1

Points
Required
Applies to
BD+C
Other versions
v4
VERTIQ reference ID
EQp3

Reviewed · Spot an error? Report it

Points

Required for Schools; no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Classroom/core-learning space schedule
  • HVAC acoustic design or test report
  • Absorptive-finish area/NRC schedule or reverberation report
  • Exterior noise assessment

Worked example

Assume a classroom has 80 m2 of ceiling area after the listed fixture exclusions. An absorptive finish route needs at least 80 m2 of qualifying surfaces with NRC at least 0.70. Providing 50 m2 of ceiling plus 30 m2 of wall treatment reaches that area test; HVAC and exterior noise still require review.1

Requirements

Schools only. Limit HVAC background noise in classrooms/core learning spaces to 40 dBA. Address exterior intrusion at high-noise sites, subject to the specified distance exemption. For reverberation, use the eligible absorptive-finish method, ANSI calculation/measurement method, or the large-volume room requirements as applicable. Historic/limited-scope exceptions are considered, while specialized acoustic spaces require professional attention and are outside this prerequisite's stated application.1

FAQ

Does a good reverberation result waive HVAC noise control?

No. The prerequisite addresses both, plus applicable exterior noise.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.