Prerequisite PBT Source Reduction: Mercury

Healthcare projects must reduce mercury-containing equipment and safely manage remaining mercury waste.1

Points
Required
Applies to
BD+C
Other versions
v4
VERTIQ reference ID
MRp2

Reviewed · Spot an error? Report it

Points

Required for Healthcare; no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Required record when applicable: Existing mercury inventory and phase-out plan for renovation projects
  • Required record when applicable: Mercury collection, storage and disposal procedure
  • Required record when applicable: USGBC PBT source reduction calculator or equivalent, with a lighting schedule showing lamp type and mercury content, plus exit-sign data
  • Preparation suggestion: Dental amalgam-separator specification where applicable

Worked example

Assume an exit sign is mercury-free and uses 4 W. It meets the sign's less-than-5-W criterion. A 5 W sign does not. The example does not demonstrate the broader equipment, lamp or dental-waste requirements.1

Requirements

Healthcare only. Define mercury product/device collection, handling and disposal. Dental facilities need qualifying amalgam separators. New construction excludes mercury-containing building equipment other than lamps; renovations need a phase-out plan. Avoid the listed prohibited lamp types, provide mercury-free exit signs below 5 W, and meet the applicable lamp mercury-content table.1

FAQ

Are all mercury-containing lamps automatically prohibited?

No. The prerequisite distinguishes prohibited lamp types from allowed lamps subject to mercury-content limits.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 91-92