Prerequisite PBT Source Reduction: Mercury
Healthcare projects must reduce mercury-containing equipment and safely manage remaining mercury waste.1
- Points
- Required
- Applies to
- BD+C
- Other versions
- v4
- VERTIQ reference ID
- MRp2
Reviewed · Spot an error? Report it
Points
Required for Healthcare; no points.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Required record when applicable: Existing mercury inventory and phase-out plan for renovation projects
- Required record when applicable: Mercury collection, storage and disposal procedure
- Required record when applicable: USGBC PBT source reduction calculator or equivalent, with a lighting schedule showing lamp type and mercury content, plus exit-sign data
- Preparation suggestion: Dental amalgam-separator specification where applicable
Worked example
Assume an exit sign is mercury-free and uses 4 W. It meets the sign's less-than-5-W criterion. A 5 W sign does not. The example does not demonstrate the broader equipment, lamp or dental-waste requirements.1
Requirements
Healthcare only. Define mercury product/device collection, handling and disposal. Dental facilities need qualifying amalgam separators. New construction excludes mercury-containing building equipment other than lamps; renovations need a phase-out plan. Avoid the listed prohibited lamp types, provide mercury-free exit signs below 5 W, and meet the applicable lamp mercury-content table.1
FAQ
Are all mercury-containing lamps automatically prohibited?
No. The prerequisite distinguishes prohibited lamp types from allowed lamps subject to mercury-content limits.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v4.1 BD+C Rating SystemFebruary 2025 download; cover dated July 28, 2023 · Printed and PDF pp. 91-92