Credit PBT Source Reduction: Lead, Cadmium, and Copper

Healthcare projects specify lower-hazard materials and compliant plumbing/joint practices.1

Points
2 points
Applies to
BD+C
Other versions
v4
VERTIQ reference ID
MRc6

Reviewed · Spot an error? Report it

Points

2 points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Preparation suggestion: Potable-water plumbing material declarations
  • Preparation suggestion: Roofing, wire/cable and paint product specifications
  • Preparation suggestion: Copper joint/soldering/flux installation specifications
  • Preparation suggestion: Renovation removal/disposal and shielding-exemption records

Worked example

Assume a potable-water fitting has a documented wetted-surface weighted average of 0.20% lead. It is below the specified 0.25% fitting limit. That document does not establish solder, flux, paint, wiring or copper-joint compliance.1

Requirements

Healthcare only. Apply the specified lead limits to potable-water solder, flux, pipes and fittings. Use lead-free roofing/flashing, electrical wire/cable below the stated lead concentration and paints without lead; manage disconnected stabilized wires in renovations. Do not use paints with intentionally added cadmium. Use permitted crimped copper joints or specified soldering/flux standards to control corrosion. Radiation-shielding lead and MRI-shielding copper are explicitly exempt.1

FAQ

Does a general 'lead free' label replace every stated test?

The credit defines specific limits and applications; verify the product against the relevant criterion.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.