EQp1 Verification of Ventilation and Filtration
Measure, inspect, and document the building's ventilation, exhaust, and filtration performance.1
- Points
- Required
- Applies to
- O+M
Reviewed · Spot an error? Report it
Points
Required prerequisite with no credit points. Residential compliance and nonresidential documentation provisions must not be conflated.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Ventilation calculations, measured flow, and filter inventory
- Outdoor-air assessment and natural opening/exhaust/economizer inspections
- Residential window/airflow, bathroom, and CO-monitor evidence
- CFR and O+M plan excerpt showing ASHRAE 62.1 Table 8-1 maintenance tasks
Worked example
Assume a 1,000 sq. ft. two-bedroom dwelling uses the printed IP airflow path. Minimum = 0.03 x 1,000 + 7.5 x (2 + 1) = 52.5 cfm. Each dwelling and its bathroom/CO-monitor requirements must be checked; this is not a whole-building compliance result.1
Requirements
Include the specified ventilation maintenance in the CFR/O+M plan, assess outdoor air quality, calculate and measure mechanical outdoor airflow, and compare results with the referenced ASHRAE minimum. For nonresidential units, document deficiencies and potential corrections; meeting minimum airflow or MERV 13 is encouraged but not mandatory under this prerequisite. Inspect and maintain natural openings, exhaust, and economizers. Residential units have mandatory window-area or minimum-airflow provisions, outdoor-venting bathroom fans or windows, and hardwired battery-backed CO monitors on each floor.1
FAQ
Must every nonresidential system already meet the ASHRAE minimum?
For this prerequisite, the source asks for comparison, circumstances, and potential corrections when nonresidential spaces are under-ventilated. The separate ventilation-performance credit requires meeting the standard. Residential minimums are mandatory.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 O+M Rating SystemJuly 2026 · EQp1, printed pp. 62-64 (PDF pp. 68-70); scorecard pp. 1-2
Maintained by VERTIQ, LEED software for consultants.