EQc5 Air Filtration

Maintain the specified filters in all applicable outdoor-air and recirculation systems.1

Points
1 point
Applies to
O+M

Reviewed · Spot an error? Report it

Points

1 point for complete applicable-system coverage and filter maintenance.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Applicable-system and filter inventory
  • MERV or ISO ePM1 performance documentation
  • Filter maintenance/replacement records and exclusions

Worked example

Assume six applicable systems all use documented MERV 13 media and follow the replacement interval. Coverage is 6/6, or 100%. Five compliant systems out of six do not establish full coverage without a valid source-listed exclusion.1

Requirements

Each ventilation system used to meet the ASHRAE ventilation rate procedure that supplies outdoor and/or recirculated air to regularly occupied spaces must use MERV 13 or higher under ASHRAE 52.2-2017, or ePM1 50% or higher under ISO 16890-2016. The specified ASHRAE 62.1-2022 Exception 6.1.4 spaces may be excluded. Maintain and replace media on the manufacturer's recommended interval.1

FAQ

Is MERV 13 only a recommendation in this credit?

This credit requires the specified MERV or equivalent ISO class in applicable systems. EQp1 separately describes the prerequisite's assessment and improvement process.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 O+M Rating SystemJuly 2026 · EQc5, printed pp. 75-75 (PDF pp. 81-81); scorecard pp. 1-2

Maintained by VERTIQ, LEED software for consultants.