EQc2 Ventilation Performance
Meet the referenced ventilation standard in all occupied spaces and document qualifying increases.1
- Points
- 3 to 5 points
- Applies to
- O+M
Reviewed · Spot an error? Report it
Points
| Points | Requirement |
|---|---|
| 3 | Meeting the referenced standard |
| 4 | 15% exceedance |
| 5 | 30% exceedance |
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Space-level ventilation calculation and referenced standard
- System outdoor-air measurements or natural-opening assessment
- 95%-coverage and increased-ventilation calculation
Worked example
Assume all occupied spaces meet their applicable minimum, and 95 of 100 equal-size regularly occupied spaces receive 130% of the referenced airflow. The increase is 30% and coverage is 95%, reaching the 5-point row if the applicable calculations and measurements comply.1
Requirements
Use the EQp1 measurements to demonstrate the applicable mechanical outdoor-air or natural-ventilation standard. The source allows the stated older ASHRAE ventilation-rate-procedure editions for mechanical spaces. When claiming increased ventilation, provide the increased airflow or natural opening sizes to 95% of regularly occupied spaces. Do not treat the prerequisite's nonresidential deficiency-documentation allowance as this credit's compliance threshold.1
FAQ
Is documenting an under-ventilated space enough for this credit?
No. The credit requires meeting the standard in occupied spaces. The nonresidential documentation approach in EQp1 is a different requirement.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 O+M Rating SystemJuly 2026 · EQc2, printed pp. 71-71 (PDF pp. 77-77); scorecard pp. 1-2