EQc1 Indoor Air Quality Performance
Use the specified continuous-monitoring and testing paths to assess indoor air quality.1
- Points
- See below
- Applies to
- O+M
Reviewed · Spot an error? Report it
Points
Up to 10 points. Continuous CO2 and PM2.5 each earn 2/3/4 on the specified monitoring/threshold scale, and TVOC monitoring earns 2. Targeted testing can earn up to 3; individual-VOC testing that meets the listed limits can earn 2.1
Exemplary performance: achieving any additional option earns 1 exemplary performance point, and reporting 12 months of Option 1 data earns 1 more, claimed under Project Priorities (EP14).2
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Monitor specifications, locations, intervals, and complete datasets
- Per-sensor percentile/daily-average analysis
- One-time test reports with locations and concurrent outdoor readings, direct-reading instrument specifications where used, and laboratory accreditation for individual-VOC tests
- Breathing-zone sensor placement confirmation and indoor air quality monitoring questionnaire
Worked example
Assume complete compliant monitoring coverage for three consecutive months. Every CO2 sensor has a 95th-percentile value of 780 ppm, every PM2.5 sensor has daily averages of 10 micrograms/m3, and TVOC is monitored as required. The continuous path gives 4 + 4 + 2 = 10 points. No duplicate one-time testing points are added.1
Requirements
Continuous monitoring covers at least three consecutive months within the reporting period, using building-grade-or-better monitors at intervals no longer than an hour, or 15 minutes for CO2. Apply each sensor's CO2 95th percentile and PM2.5/TVOC daily-average requirements. Targeted one-time testing requires concurrent outdoor measurements and prescribed methods; each two compliant parameters earn 1 point, up to 3. The individual-VOC path requires the listed contaminants, accredited laboratory methods, investigation/correction/retesting where applicable, and its stated limits. Do not double-count the same parameter between continuous and targeted one-time testing.1
FAQ
Can one PM2.5 result earn points under monitoring and targeted testing?
The source prohibits earning both continuous-monitoring and targeted one-time-testing points for the same parameter. Keep paths and parameters distinct.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 O+M Rating SystemJuly 2026 · EQc1, printed pp. 67-70 (PDF pp. 73-76); scorecard pp. 1-2