EAp3 Minimum Energy Performance

Meet the minimum energy requirement using the path permitted for the building type and location.1

Points
Required
Applies to
O+M

Reviewed · Spot an error? Report it

Points

Required prerequisite with no credit points. An ENERGY STAR score of 60 satisfies this path's numerical minimum, while credit EAc2 starts at a higher score.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • ENERGY STAR score and Data Verification Checklist aligned to the reporting period, or applicable EUI target calculation
  • Current and qualifying historical 12-month energy data
  • Occupancy, normalization, and high-process-load evidence where applicable

Worked example

Assume the historical path is permitted, occupancy is comparable, and the valid baseline is 1,000,000 kWh-equivalent of annual site energy. Current use of 900,000 gives (1,000,000 - 900,000) / 1,000,000 = 10% reduction, above the ordinary 8% minimum.1

Requirements

Eligible U.S. and Canadian property types use ENERGY STAR and must score at least 60. Eligible types outside those countries may use ENERGY STAR or EUI targets; the ENERGY STAR location must have the prescribed comparable climate. Ineligible Appendix II property types may use EUI targets or a historical baseline. Other types use the historical route or applicable additional guidance. Historical comparison normally requires at least 8% site- or source-energy reduction against a comparable 12-month baseline within eight years; a 4% threshold requires all high-process-load criteria.1

FAQ

May every building choose the historical route?

No. The source assigns eligible paths by ENERGY STAR eligibility, geography, and Appendix II classification. Check that assignment before using a reduction example.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 O+M Rating SystemJuly 2026 · EAp3, printed pp. 33-34 (PDF pp. 39-40); scorecard pp. 1-2; Appendix II, printed pp. 85-87

Maintained by VERTIQ, LEED software for consultants.