EAp3 Minimum Energy Performance
Meet the minimum energy requirement using the path permitted for the building type and location.1
- Points
- Required
- Applies to
- O+M
Reviewed · Spot an error? Report it
Points
Required prerequisite with no credit points. An ENERGY STAR score of 60 satisfies this path's numerical minimum, while credit EAc2 starts at a higher score.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- ENERGY STAR score and Data Verification Checklist aligned to the reporting period, or applicable EUI target calculation
- Current and qualifying historical 12-month energy data
- Occupancy, normalization, and high-process-load evidence where applicable
Worked example
Assume the historical path is permitted, occupancy is comparable, and the valid baseline is 1,000,000 kWh-equivalent of annual site energy. Current use of 900,000 gives (1,000,000 - 900,000) / 1,000,000 = 10% reduction, above the ordinary 8% minimum.1
Requirements
Eligible U.S. and Canadian property types use ENERGY STAR and must score at least 60. Eligible types outside those countries may use ENERGY STAR or EUI targets; the ENERGY STAR location must have the prescribed comparable climate. Ineligible Appendix II property types may use EUI targets or a historical baseline. Other types use the historical route or applicable additional guidance. Historical comparison normally requires at least 8% site- or source-energy reduction against a comparable 12-month baseline within eight years; a 4% threshold requires all high-process-load criteria.1
FAQ
May every building choose the historical route?
No. The source assigns eligible paths by ENERGY STAR eligibility, geography, and Appendix II classification. Check that assignment before using a reduction example.1
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 O+M Rating SystemJuly 2026 · EAp3, printed pp. 33-34 (PDF pp. 39-40); scorecard pp. 1-2; Appendix II, printed pp. 85-87
Maintained by VERTIQ, LEED software for consultants.