EAp2 Energy Monitoring and Reporting

Track each building energy source and report monthly use for a complete 12-month period.1

Points
Required
Applies to
O+M

Reviewed · Spot an error? Report it

Points

Required prerequisite with no credit points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Energy meter and delivered-fuel inventory
  • 12-month monthly energy-use records by source
  • Tenant-meter exclusions and corresponding area calculation
  • Meter calibration confirmation, ongoing annual reporting commitment, and method of data sharing

Worked example

Assume excluded tenant meters serve 8,000 square feet of a 100,000-square-foot building. The exclusion is 8%, within the 10% allowance, and intensity calculations use 92,000 square feet. This does not waive the remaining source, monthly-data, calibration, or reporting requirements.1

Requirements

Use permanent meters or submeters for total building use by source. Track unmetered delivered fuels by delivery date and quantity. Calibrate meters under the owner's or management's control as recommended by the manufacturer. Tenant meters may be excluded for up to 10% of gross building area only when the corresponding area is also removed from intensity calculations. Commit to annual reporting of monthly energy data after certification.1

FAQ

Can excluded tenant area stay in the intensity denominator?

No. The source couples the permitted tenant-meter exclusion with removal of the associated area from energy-use or GHG-intensity calculations.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v5 O+M Rating SystemJuly 2026 · EAp2, printed pp. 32-32 (PDF pp. 38-38); scorecard pp. 1-2

Maintained by VERTIQ, LEED software for consultants.