EAc3 Enhanced Refrigerant Management Performance
Compare GWP-weighted leaked refrigerant with the total installed full-charge refrigerant mass.1
- Points
- 1 to 2 points
- Applies to
- O+M
Reviewed · Spot an error? Report it
Points
| Points | Requirement |
|---|---|
| 1 | A ratio of 50 or less |
| 2 | 25 or less |
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Full-charge refrigerant inventory and GWP values
- Reporting-period leakage and recharge log
- Leakage-emissions-ratio calculation and district-energy scope
- Attestation that all refrigerant equipment is in the inventory and leakage tracking, or narrative of allowed exclusions
Worked example
Assume one system has a full charge of 100 kg, refrigerant GWP 1,000, and 2 kg leaked during the period. Ratio = (1,000 x 2) / 100 = 20, meeting the 2-point threshold. The denominator is charge mass; no extra multiplication by 100 is used.1
Requirements
For the 12-month reporting period, sum each refrigerant's GWP multiplied by the mass leaked and divide by total full-charge refrigerant mass, using consistent mass units. This is the refrigerant leakage emissions ratio. A project with neither refrigerant equipment nor district thermal energy generated with refrigerant equipment automatically reaches the two-point threshold.1
FAQ
Is this just the percentage of charge leaked?
No. The numerator is weighted by refrigerant GWP. Two refrigerants with the same mass leakage percentage can therefore produce different ratios.1