EQp3 No Smoking
Prevent smoke from entering project spaces through the applicable building and tenant smoking restrictions.1
- Points
- Required
- Applies to
- ID+CO+M
Reviewed · Spot an error? Report it
Points
Required prerequisite; no points. Choose the route appropriate to the building's smoking-law and policy context.1
Documents to prepare
Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.
- Preparation: Applicable law or landlord smoking policy
- Preparation: Signage and designated-area plan
- Preparation: Smoke-migration and enforcement documentation for the selected option
Worked example
Assume local code permits the full 25-ft outdoor separation and a designated area is 30 ft from every affected opening and intake. The distance margin is 5 ft. Indoor prohibitions, communication and smoke-migration controls still require their own evidence.1
Requirements
Option 1 locates the project in a building with indoor smoking prohibited by law or landlord policy, communicated by the applicable law or permanent signage. Prohibit outdoor smoking except in designated areas at least 25 ft from project entrances, air intakes and operable windows, or the maximum distance local codes allow.1
Option 2 prohibits smoking in project spaces, common areas used by project occupants and areas served by the same HVAC system. Prevent mechanical or natural smoke migration and communicate and enforce the policy or provide signage. The July addendum identifies ceremonial cultural practices involving tobacco or other controlled materials as exempt.12
FAQ
Sources
This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.
- LEED v5 ID+C Rating SystemJuly 2026 · EQp3; printed pp. 90-90, PDF pp. 95-95; scorecard printed pp. 1-2, PDF pp. 6-7
- LEED v5 ID+C Addenda Table, cumulativeJuly 31, 2026; individual post dates identified in locator · PDF p. 9, EQp3 Requirements Explained, Outdoor Smoking; July 31, 2026 ceremonial cultural practices exception
Maintained by VERTIQ, LEED software for consultants.