EAc2 Reduce Peak Thermal Loads

Reduce peak heating/cooling demand using envelope, ventilation, thermal-bridging, and peak-load strategies. Annual energy savings alone do not establish this credit.1

Points
Up to 5
Applies to
BD+C

Reviewed · Spot an error? Report it

Points

NC and Core and Shell: maximum 5 points. General Options 1/2/3 each earn 1, while Option 4 earns 1-3. Residential infiltration/balanced ventilation earns 2. Under Option 4 simulation, peak-load PI values 0.5/0.4/0.3 correspond to 1/2/3 points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Envelope compliance and thermal-bridge detail set
  • Air-leakage test and testing/adjusting/balancing reports
  • Ventilation recovery equipment specifications
  • Peak heating/cooling load model and baseline/proposed comparison

Worked example

Assume Option 4 simulation, a permitted baseline combined coincident peak of 1,000 kW and proposed combined peak of 400 kW under the required model conditions. PI = 400/1,000 = 0.40, reaching 2 points in Table 4, provided measured leakage, ventilation, envelope, and other requirements are satisfied.1

Requirements

Every option preserves the specified envelope prescriptive or envelope trade-off compliance, without trading envelope performance against other systems. Options address balanced ventilation and measured air leakage; qualifying ventilation heat/enthalpy recovery; prescribed thermal-bridge details; or peak thermal-load reduction using a permitted design tool, trade-off method, or simulation. Option 4 includes ventilation loads, measured leakage, and balanced-ventilation conditions. Residential and Core and Shell provisions differ.1

FAQ

Can annual energy-model savings be substituted for peak loads?

No. The peak-load paths use the stated peak-demand metrics and supporting model/test conditions.1