Credit PBT Source Reduction: Mercury

Healthcare projects specify and install fluorescent lamps that combine low mercury content with long lamp life, going beyond the mercury prerequisite.1

Points
See below
Applies to
BD+C
Other versions
v4.1
VERTIQ reference ID
MRc9

Reviewed · Spot an error? Report it

Points

1 point, Healthcare only. The mercury prerequisite is required separately and earns no points.1

Documents to prepare

Prepared by VERTIQ as a checklist. Check the Reference Guide for what your review requires.

  • Lighting schedule with lamp type, ballast type, mercury content and rated life hours
  • Narrative explaining any lamps excluded from the credit
  • PBT source reduction calculator or equivalent documentation

Worked example

Assume a four-foot T-8 lamp on an instant start ballast has 3 mg of mercury and 35,000 rated hours at 3-hour starts. It is below the 3.5 mg maximum and above the 30,000-hour minimum for that lamp and ballast type. Repeat the check for every other lamp type in the lighting schedule.1

Requirements

Healthcare only. Specify and install fluorescent lamps with both the low mercury content set by the PBT Source Reduction: Mercury prerequisite and the long lamp life listed in Table 1.1

Table 1 sets rated life by lamp type, at 3-hour starts for fluorescent lamps where stated. Eight-foot T-8 lamps (10 mg mercury maximum) need 24,000 rated hours for standard output on instant start ballasts, or 18,000 hours for high output on instant start or program start ballasts. Four-foot T-8 lamps (3.5 mg) need 30,000 hours on instant start or 36,000 hours on program start ballasts. Two-foot and three-foot T-8 lamps (3.5 mg) need 24,000 hours. U-bent T-8 lamps (6 mg) need 18,000 hours on instant start or 24,000 hours on program start ballasts. Linear T-5 lamps (2.5 mg) need 25,000 hours on program start ballasts.1

Compact fluorescent lamps with nonintegral ballasts (3.5 mg) need 12,000 rated hours. ENERGY STAR qualified compact fluorescent lamps with integral ballasts (3.5 mg) need 10,000 hours as bare bulbs, or 8,000 hours for covered models such as globes, reflectors and A-19s. For high-pressure sodium lamps (10 mg up to 400 watts, 32 mg above 400 watts), use the noncycling type or replace them with LED or induction lamps.1

Do not specify or install circular fluorescent lamps or probe start metal halide lamps.1

FAQ

Does this credit replace the mercury prerequisite?

No. The credit builds on the prerequisite's low-mercury limits and adds lamp-life criteria.1

Is this credit part of construction waste management?

No. It addresses lamp mercury content and lamp life. Healthcare projects pursue Construction and Demolition Waste Management as a separate credit.1

Sources

This reference summarizes the cited material. It does not replace the applicable rating system, addenda or a GBCI review.

  1. LEED v4 BD+C Rating SystemUpdated July 25, 2019 · PBT Source Reduction: Mercury credit, printed/PDF pp. 99-100, Table 1